Model GS202P, 14.0 K-factor Pendent Sprinklers Fast Response
GENERAL DESCRIPTION
- The GS Model GS202P, K-factor Pendent Sprinklers are Fast They are suppression- mode sprinklers that are especially
advantageous as a means of eliminating the use of in-rack sprinklers when protecting high piled storage.
Model GS202P Sprinklers are primarily designed for protection of the following storage arrangements:
• Most encapsulated or non encapsulated common materials including cartoned, unexpanded plastics.
• Some storage arrangements of rubber tires, roll paper, flammable liquids

TECHNICAL DATA
-
Model: GS202P
-
K-Factor: 14.0 (201.6 L/min/bar¹⁄²)
-
Response Type: Fast Response (3 mm bulb)
-
Mounting Orientation: Pendent / Upright
-
Thread Size: 3/4” NPT
-
Max Working Pressure: 175 psi (12 bar)
- Temperature Rating ºF (ºC): 155°F (68°C) 200°F (93°C)
- Construction & Materials
- Frame: Brass
-
- Deflector: Bronze
- Compression Screw: Bronze
- Button: Brass
- Bulb: 3 mm Glass (Q3 – Fast Response)
- Seal: TEFLON
INSTALLATION
- GS Model GS202P Pendent Sprinklers must be installed in accordance with this section.
- General Instructions
- Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present.
- A leak-tight 3/4 in. NPT sprinkler joint can be achieved by applying a minimum-to-maximum torque of 10 to 20 lb-ft (13,4 to 26,8 N∙m). Higher levels of torque can distort the sprinkler inlet with consequent leakageor impairment of the sprinkler.
NOTE
- Step 1. With pipe thread sealant applied, hand tighten the sprinkler into the sprinkler fitting.
- Step 2. Wrench-tighten the Model GS202P /GS202U Sprinkler using only the W-Type 34 Sprinkler Wrench as shown in Figure 2, and by fully engaging (seating) the wrench on the sprinkler wrench flats as shown in Figure 1.
- Step 3. After installation, inspect the bulb of each Model GS202P/ GS202U Sprinkler for damage. In particular, verify that the bulb is not cracked. Replace damaged sprinklers.