Model GS202P, 14.0 K-factor Upright Sprinklers Fast Response

GENERAL DESCRIPTION

  • The GS Model GS202U, K-factor Upright Sprinklers are Fast They are suppression- mode sprinklers that are especially
    advantageous as a means of eliminating the use of in-rack sprinklers when protecting high piled storage.
    Model GS202P Sprinklers are primarily designed for protection of the following storage arrangements:
    • Most encapsulated or non encapsulated common materials including cartoned, unexpanded plastics.
    • Some storage arrangements of rubber tires, roll paper, flammable liquids
K=14 Đầu phun quay lên GS202U - phản ứng nhanh
K=14 Đầu phun quay lên GS202U – phản ứng nhanh

TECHNICAL DATA

  • Model: GS202U

  • K-Factor: 14.0 (201.6 L/min/bar¹⁄²)

  • Response Type: Fast Response (3 mm bulb)

  • Mounting Orientation: Upright

  • Thread Size: 3/4” NPT

  • Max Working Pressure: 175 psi (12 bar)

  • Temperature Rating ºF (ºC):  155°F (68°C) 200°F (93°C)
  • Construction & Materials
    • Frame: Brass
    • Deflector: Bronze
    • Compression Screw: Bronze
    • Button: Brass
    • Bulb: 3 mm Glass (Q3 – Fast Response)
    • Seal: TEFLON

INSTALLATION

  • GS Model GS202U Upright Sprinklers must be installed in accordance with this section.
  • General Instructions
    • Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present.
    • A leak-tight 3/4 in. NPT sprinkler joint can be achieved by applying a minimum-to-maximum torque of 10 to 20 lb-ft (13,4 to 26,8 N∙m). Higher levels of torque can distort the sprinkler inlet with consequent leakageor impairment of the sprinkler.

NOTE 

  •  Step 1. With pipe thread sealant applied, hand tighten the sprinkler into the sprinkler fitting.
  • Step 2. Wrench-tighten the Model GS202P /GS202U Sprinkler using only the W-Type 34 Sprinkler Wrench as shown in Figure 2, and by fully engaging (seating) the wrench on the sprinkler wrench flats as shown in Figure 1.
  • Step 3. After installation, inspect the bulb of each Model GS202P/ GS202U Sprinkler for damage. In particular, verify that the bulb is not cracked. Replace damaged sprinklers.

Reviews

There are no reviews yet.

Be the first to review “Upright Sprinklers Fast Response Model GS202U, 14.0 K-factor”

Email của bạn sẽ không được hiển thị công khai. Các trường bắt buộc được đánh dấu *