GENERAL DESCRIPTION
The GS fire Sprinkler of the ESFR-202 type are fast acting irrigation systems for early fire suppression, having a nominal k-factor 202 (14.0) respectively and operating in fire suppression mode.They are best used as ameans of protecting high-capacitywarehouses without theuseof in-rackirrigationsystems.
NOTICE
The GS fire Sprinkler of the 14.0 K-factor Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of local, in addition to the standards of any other authorities having jurisdiction.
Failure to do so may impair the performance of these devices.
The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions.
OPERATION
The GS fire Sprinkler of the ESFR-202/GS202U and GS202P Sprinklers uses a fusible alloy welding element. When the temperature rises to the operating temperature, the fusible alloy melts, causing the metalsheet toseparate, and then all the support parts are detached from the nozzle frame, opening thewater channel, and distributing water through the splashtray.

PHYSICAL CHARACTERISTIC
Frame : Brass
Deflector : Stainless steel
Sealing Assembly: NBR
Sensing Element : Fusible Alloy
Screw: Stainless steel
Temperature Sensing Element: Fusible Alloy
INSTALLATION
1.Before installation, all installation personnel must be trained;
2.The nozzle must be unpacked and checked before installation to eliminate transportation damage; 3.Please use the original packaging box for storage and transportation. In any case, each wine nozzle should be placed separately to prevent mutual damage;
4.The nozzle must not bump during installation; The sprinkler installation site is not allowed to cross construction, cross construction may cause damage to the sprinkler;
5.It is strictly prohibited to install the nozzle on the short riser stacking, moving;
6.The sprinkler installation should be in the system after pressure test, flushing qualified;
7.The sprinkler must be installed using a fixed bracket with the appropriate opening size, do not use adjustable wrenches or pipe clamps. The maximum installation torque of the nozzle shall not be greater than 25N•m;
8.The nozzle connection thread is strictly prohibited from using hemp, should use polytetrafluoroethylene (commonly known as raw material tape) or non-curing pipe thread connection agent
9.When installing the sprinkler head, the sprinkler after removing the protective clip, check the nozzle carefully. If the frame and splash tray of the nozzle are deformed or the release element is damaged and deformed, the nozzle of the same specification and model should be replaced.