Model GS218, 11.2 K-factor Horizontal Sidewall Sprinklers Quick Response.
Horizontal sidewall sprinklers aredesigned for installationalongawall or thesideof abeamand are commonly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations, where piping across theceiling isnotdesirable.
Corrosion resistant coatings, whereapplicable,are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres.
Consequently, it is recommended that theend user be consulted with respect to the suit-ability of these corrosion resistant coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, asaminimum, a long with the corrosive nature of the chemical to which the sprinklers will be exposed.
NOTICE
The Model GS216/ GS218 Sprinklers described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protection Association (NFPA), inaddition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of the sedevices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.

TECHNICAL DATA:
Sprinkler Identification: GS218
K-factor, gpm/psi½ (Lpm/bar½): 11.2 (161 L/min/bar¹⁄²)
Temperature Rating ºF (ºC): 155°F (68°C) 200°F (93°C) 286°F(141°C)
Thread Size: 3/4 in. NPT
Sprinkler Orientation: Horizontal
Maximum Working Pressure, psi (bar): 175 psi (12 bar.
Sprinkler Identification
Frame : Brass
Deflector : .Brass
Compression Screw : Brass
Plug : Brass
Bulb (5 mm/3mm) : Glass
Sealing Assembly : Rubber
Operation
The glass bulb contains a fluid that expands when exposed to heat.When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Installation :
- Horizontal Sprinklers (GS218): Install with the frame arms parallel to the branch line.
- Use the appropriate sprinkler wrenches to prevent damage during installation.
- Maintain proper clearance from obstructions as per local fire codes and regulations.
Note:
- Step 1. With pipe thread sealant applied, hand-tighten the sprinkler into the sprinkler fitting.
- Step 2. Wrench-tighten the Model GS216/ GS218 Sprinkler using only the W-Type 34 Sprinkler Wrench as shown in Figure 2, and by fully engaging (seating) the wrench on the sprinkler wrench flats
- Step 3. After installation, inspect the bulb of each Model GS216/ GS218 Sprinkler for damage. In particular, verify that the bulb is not cracked. Replace damaged sprinklers.